Module 2 · 30 minutes

Understanding the residential system

Follow power from the transformer to the load and understand a 120/240 V split-phase system.

Learning objectives

By the end, you should be able to:

  • Trace the power path from utility transformer to branch-circuit load
  • Explain the relationship among L1, L2, and neutral
  • Distinguish neutral from equipment grounding conductors

Follow the power path

Utility transformer → service conductors → meter → service disconnect → panel → breaker → branch circuit → load

A typical dwelling receives a 120/240 V single-phase, 3-wire supply. The center-tapped transformer secondary gives us two ungrounded conductors and one grounded conductor.

MeasurementNominal voltage
L1 to neutral120 V
L2 to neutral120 V
L1 to L2240 V

Make it intuitive

A straight 240 V load uses L1 and L2 and ordinarily does not need the neutral. Equipment such as a range may need a neutral because some internal components operate at 120 V even though the heating elements use 240 V.

The neutral is a normal current-carrying circuit conductor. The equipment grounding conductor normally carries no current; it provides an effective path during a ground fault.

Field check

Sketch a service, panel, two-pole breaker, and straight 240 V water heater. Label every conductor and explain why the heater does or does not require a neutral.